Smart Cabinet Distribution Unit Advanced Operations 59
Installation and Operations Manual
Setting the Infeed Load limit:
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Smart CDU: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value
from 0 to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25
amperes, using the infeed’s absolute name:
Smart CDU: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling the Temp trap:
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the Smart CDU: prompt, type set trap ths temp, followed by the sensor name and on or off. Press
Enter.
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
Smart CDU: set trap ths temp .a1 on<Enter>
Setting the Temperature sensor threshold limits:
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and
upper threshold limits for the Temperature sensor.
To set the Temperature threshold limits:
At the Smart CDU: prompt, type set trap ths, templow or temphigh, followed by the sensor name and
a value from 0 to 127 in degrees Celsius. Press Enter.
Example
The following command sets the second temperature high threshold limit to 95:
Smart CDU: set trap ths temphigh .a2 95<Enter>
Configuring Temperature Recovery Delta:
The Temperature Recovery Delta command allows configuration of the number of degrees of change
needed to recover from a temperature alarm. For more information about the recovery delta, see
Configuring Temperature Recovery Delta: on page 21.
To configure the temperature recovery delta:
At the Smart CDU: prompt, type set event temp tempdelta, followed by the sensor name, the number
of degrees for the recovery delta, and press Enter.
NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for
Fahrenheit. The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
Example
The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity
sensor .A1:
Smart CDU: event temp tempdelta temp_humid_sensor_A1 2<Enter>
Enabling or Disabling the Humid trap:
The Set Trap THS Humid command is used to enable or disable the Humid trap.
To Enable or Disable the Humid trap:
At the Smart CDU: prompt, type set trap ths humid, followed by the sensor name and on or off. Press
Enter.
Example
The following command enables the Humid trap for the first temperature-humidity sensor:
Smart CDU: set traps ths humid .a1 on<Enter>