Smart Cabinet Distribution Unit Advanced Operations • 55
Installation and Operations Manual
Setting the Trap community string:
The Set SNMP Trapcomm command is used to set the community string that is included with all
generated traps. This string must be defined to enable trap generation.
The trap community string may be 1 to 24 characters.
The default Trapcomm string is “trap”.
To set the Trapcomm community string:
At the Smart CDU: prompt, type set snmp trapcomm, followed by the string and press Enter.
Displaying SNMP configuration information:
The Show SNMP command displays all SNMP configuration information.
• SNMP support status
• SNMP community strings
• Trap timer value
• Trap destinations
To display SNMP configuration information:
At the Smart CDU: prompt, type show snmp and press Enter.
Example
The following command displays the SNMP configuration information:
Smart CDU: show snmp<Enter>
SNMP Configuration
SNMP: Enabled
GET Community String: public
SET Community String: private
TRAP Community String: trap
Error Trap Repeat Time (seconds): 180 seconds
Trap Destination 1: 64.42.31.208
Trap Destination 2: snmp.servertech.com
IP Restrictions: Trap Destinations Only
SysName: No Name
SysLocation: No Location
SysContact: No Contact
SNMP Traps
The Smart CDU supports four types of SNMP traps. Traps are enabled at the Tower (T), Infeed (I),
Environmental Monitor (E) or sensor (S) level.
Trap Summary
Name Level(s) Description
Status T, I, O, E, S Operational status change
Load I Input load out of limit
Temp S Temperature is out of range
Humid S Relative Humidity is out of range
All traps include the Location of the Sentry as defined with the Set Location command.