Smart Cabinet Distribution Unit Operations • 21
Installation and Operations Manual
Configuring input feed traps:
Click on the Input Feed Traps link.
On the subsequent Input Feed Traps page, select or deselect the desired traps and press Apply.
For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and press Apply.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Enabling or disabling Environmental Monitor traps:
Click on the Environmental Monitor Traps link.
On the subsequent page, select or deselect the desired traps and press Apply.
Configuring the Temperature and Relative Humidity sensor traps:
Click on the Sensor Traps and Thresholds link.
On the subsequent Sensor Traps and Thresholds page, select or deselect the desired trap checkboxes
and press Apply.
Configuring the Temperature and Relative Humidity sensor thresholds:
Click the Sensor Traps and Thresholds link.
For temperature thresholds, type a low and high temperature value in the Low Temp and High temp
fields and press Apply.
For relative humidity thresholds, type a low and high humidity percentage in the Low Humid and High
Humid fields, and press Apply.
NOTE: For temperature thresholds, the valid range is 0 to 123 in degrees Celsius or 32 to 254 in degrees Fahrenheit.
For relative humidity, the valid range is 0 to 100 (in percent relative humidity).
Configuring Temperature Recovery Delta:
Click on the Sensor Traps and Thresholds link.
The Recovery Delta field allows configuration of the number of degrees of change needed to recover
from a temperature alarm. After exceeding the high-temperature threshold, the temperature value must
fall below the high-temperature threshold by the number of degrees specified in the Recovery Delta
field before the sensor recovers.
For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2
degrees Fahrenheit, the sensor will not recover until a temperature value of 78 degrees Fahrenheit is
reported.
To configure a temperature recovery delta, type a value (in degrees) in the Recovery Delta field and
press Apply.
NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for
Fahrenheit. The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
LDAP
The LDAP configuration page is used for setup and maintenance of all settings required to enable
LDAP support. For additional information and configuration requirements, see
LDAP on page 61.
Enabling or disabling LDAP support:
Select Enabled or Disabled from the LDAP drop-down menu and press Apply.
Changing the LDAP server port:
Enter the port number in the LDAP Port field and press Apply.
Setting the LDAP server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and press Apply.
Enabling or disabling LDAP over TLS/SSL:
Select Yes or No from the Use TLS/SSL drop-down menu and press Apply.
NOTE: If LDAP over TLS/SSL is enabled, MD5 binding is disabled.