Server Technology PT40 Manual de instalación Pagina 58

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 90
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 57
58 Advanced Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Configuring Traps
SNMP Trap Command Summary
Command Description
Set Trap Tower Status Enables or disables the Tower Status trap
Set Trap Infeed Status Enables or disables the Infeed Status trap off
Set Trap Infeed Load Enables or disables the Infeed Load trap
Set Trap Infeed HighThresh Sets the Infeed Load trap high limit
Set Trap EM Status Enables or disables the Environmental Monitor Status trap
Set Trap THS Status Enables or disables a temperature/humidity sensor Status trap
Set Trap THS Temp Enables or disables a temperature/humidity sensor Temp trap
Set Trap THS Temp Delta Sets temperature recovery delta
Set Trap THS Temphigh Sets a temperature/humidity sensor Temp trap high limit
Set Trap THS Templow Sets a temperature/humidity sensor Temp trap low limit
Set Trap THS Humid Enables or disables a temperature/humidity sensor Humid trap
Set Trap THS Humidhigh Sets a temperature/humidity sensor Humid trap high limit
Set Trap THS Humidlow Sets a temperature/humidity sensor Humid trap low limit
Show Traps Displays trap configurations
Enabling or Disabling a Status trap:
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.
To Enable or Disable a Status trap:
At the Smart CDU: prompt, type set trap (tower, infeed, em or ths) status, followed by the tower,
infeed or outlet name, and on or off. Press Enter, or\
Type set trap (tower, infeed, em or ths) Status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Smart CDU: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
Smart CDU: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet
Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is
disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.
Enabling or Disabling a Load trap:
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Smart CDU: prompt, type set trap infeed load, followed by the infeed name, and on or off. Press
Enter, or
Type set trap infeed load all, followed by on or off and press Enter.
Examples
The following command enables the Load trap for second infeed on the first tower, using the infeed’s
absolute name:
Smart CDU: set trap infeed load .AB on<Enter>
The following command disables the Load trap for all infeeds:
Smart CDU: set trap infeed load all off<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed
Load trap automatically enables the Infeed and Tower Status traps for that infeed.
Vista de pagina 57