20 Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Enabling or disabling the FTP server:
The Sentry features the ability to upload and download system configuration files to ease
implementation across multiple Sentry devices. See
Chapter 4: Advanced Operations -
Upload/Download for more information on configuration upload and download.
Select Enabled or Disabled from the drop-down menu and press Apply.
NOTE: The FTP server must be enabled for configuration upload or download.
SNTP/Syslog
The SNTP/Syslog configuration page is used for setup and maintenance of SNTP and Syslog support.
For additional information and configuration requirements for Syslog support, see
Logging on page 73.
Setting the SNTP server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and press Apply.
Setting the Local GMT offset:
Select the local offset from GMT value from the drop-down menu and press Apply.
Setting the Syslog server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and press Apply.
Changing the Syslog server port number:
In the Syslog Port field, enter the port number and press Apply.
SNMP/Thresholds
The SNMP/Thresholds configuration page is used for setup and maintenance of all settings required to
enable SNMP support, and to provide access to the trap configuration pages. For additional information
on SNMP support and detailed descriptions of available traps, see
SNMP on page 53.
NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the
Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal.
Enabling or disabling SNMP support:
Select Enabled or Disabled from the drop-down menu and press Apply.
Setting the community strings:
Enter the community string in the appropriate field and press Apply.
Community strings may be 1 to 24 characters
Setting the trap timer:
Enter a trap timer value in the Error Trap Repeat Time field and press Apply.
The Error Trap Repeat Time value may be 1 to 65535 (in seconds).
Setting trap destinations:
Enter an IP address or hostname in the appropriate Trap Destination field and press Apply.
Setting IP Restrictions:
Select No Restrictions or Trap Destinations Only from the IP Restrictions drop-down menu and press
Apply.
NOTE: When Trap Destinations Only is selected, SNMP Manager GET and SET requests are only allowed from the IP
addresses of the defined traps destinations.
Setting the SNMP SysName, SysLocation or SysContact objects:
In the appropriate field, enter the SysName, SysLocation or SysContact objects and press Apply.
Enabling or disabling tower traps:
Click on the Tower Traps link.
On the subsequent Tower Traps page, select or deselect the desired traps and press Apply.