Displaying outlet information
The Show Outlets command displays information about all outlets. This information includes:
• Sequencing and reboot timer values
• Descriptive outlet name, if applicable
• Outlet wakeup state and Post-On settings
To display outlet information:
At the Sentry: prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
Sentry: show outlets<Enter>
Outlet Outlet Wakeup Post-On
ID Name State Delay (seconds)
.A1 TowerA_Outlet1 On 0
.A2 TowerA_Outlet2 On 0
.A3 FileServer_1 On 0
.A4 On 90
Outlet Options:
Sequence Interval: 2 seconds
Reboot Delay: 15 seconds
Group Administration
Creating a group name
The Create Group command creates a new group name.
To create a group name:
At the Sentry: prompt, type create group, optionally followed by a descriptive name of up to 24
alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed. Group
names are not case sensitive). Press Enter.
Example
The following command creates group name ServerGroup_1:
Sentry: create group ServerGroup_1<Enter>
Removing a group name
The Remove Group command removes a group name.
To remove a group name:
At the Sentry: prompt, type remove group, optionally followed by a username. Press Enter.
Example
The following command removes group name ServerGroup_1:
Sentry: remove group ServerGroup_1<Enter>
Sentry Commander - PT40 Operations • 33
Installation and Operations Manual